Below is the complete layout, formulas, and a step-by-step guide. Sheet 1: Input Data & Summary | Project Name: | Office Building Example | Date: | 15-Apr-2026 | | :--- | :--- | :--- | :--- | | Location: | New York | By: | HVAC Engineer | | Outdoor Summer DB: | 95 °F | Indoor Design DB: | 75 °F | | Outdoor Summer WB: | 78 °F | Indoor RH: | 50% | | Daily Range: | M | Elevation: | 0 ft | Summary of Loads (BTU/hr) | Load Type | Sensible (BTU/hr) | Latent (BTU/hr) | Total (BTU/hr) | | :--- | :--- | :--- | :--- | | Roof | 4,500 | 0 | 4,500 | | Walls (External) | 6,200 | 0 | 6,200 | | Glass (Conduction) | 3,100 | 0 | 3,100 | | Glass (Solar Radiation) | 8,500 | 0 | 8,500 | | People | 4,200 | 4,800 | 9,000 | | Lighting | 5,600 | 0 | 5,600 | | Equipment / Appliances | 7,500 | 2,000 | 9,500 | | Infiltration / Ventilation | 10,800 | 12,000 | 22,800 | | Total Load | 50,400 | 18,800 | 69,200 | | Safety Factor (10%) | 5,040 | 1,880 | 6,920 | | Grand Total | 55,440 | 20,680 | 76,120 |

Function GetCLTD(WallType As String, Hour As Integer) As Double ' Simplified CLTD table for light-weight wall, July, 40°N latitude Dim CLTD_Table(1 To 24) As Double CLTD_Table(1) = 5: CLTD_Table(2) = 4: CLTD_Table(3) = 3: CLTD_Table(4) = 2 CLTD_Table(5) = 2: CLTD_Table(6) = 3: CLTD_Table(7) = 6: CLTD_Table(8) = 10 CLTD_Table(9) = 14: CLTD_Table(10) = 18: CLTD_Table(11) = 21: CLTD_Table(12) = 23 CLTD_Table(13) = 24: CLTD_Table(14) = 24: CLTD_Table(15) = 23: CLTD_Table(16) = 21 CLTD_Table(17) = 19: CLTD_Table(18) = 17: CLTD_Table(19) = 14: CLTD_Table(20) = 11 CLTD_Table(21) = 8: CLTD_Table(22) = 6: CLTD_Table(23) = 6: CLTD_Table(24) = 5 GetCLTD = CLTD_Table(Hour) End Function heat load calculation sheet xls

I have designed a comprehensive format that follows the principles of the ASHRAE (CLTD/CLF) method and the basic Carrier HAP approach . You can copy the tables below directly into Excel. Below is the complete layout, formulas, and a

= Grand Total Sensible / (1.08 x (Room Temp - Supply Temp)) Assuming supply temp = 55°F → 55,440 / (1.08 x 20) = 2,567 CFM Sheet 2: Detailed Wall / Window Calculation Table | Element | Orientation | Area (sq.ft) | U-Value | CLTD / ΔT | Cooling Load (BTU/hr) | Formula | | :--- | :--- | :--- | :--- | :--- | :--- | :--- | | Roof | Horizontal | 2,000 | 0.05 | 45 | 4,500 | Area x U x CLTD | | North Wall | N | 400 | 0.10 | 10 | 400 | Area x U x CLTD | | South Wall | S | 400 | 0.10 | 25 | 1,000 | Area x U x CLTD | | East Wall | E | 300 | 0.10 | 30 | 900 | Area x U x CLTD | | West Wall | W | 300 | 0.10 | 35 | 1,050 | Area x U x CLTD | | Glass North | N | 120 | 1.10 | 12 | 1,584 | Area x U x CLTD | | Glass South | S | 120 | 1.10 | 15 | 1,980 | Area x U x CLTD | | Glass East | E | 80 | 1.10 | 18 | 1,584 | Area x U x CLTD | | Glass West | W | 80 | 1.10 | 20 | 1,760 | Area x U x CLTD | | Solar Load Glass | S | 120 | SCL=200 | | 8,000 | Area x SCL x Shading | | Solar Load Glass | E | 80 | SCL=150 | | 3,600 | Area x SCL | Note: CLTD = Cooling Load Temperature Difference (from ASHRAE table). SCL = Solar Cooling Load factor. Sheet 3: Internal Loads & Infiltration | Source | Quantity | Sensible (BTU/hr per unit) | Latent (BTU/hr per unit) | Total Sensible | Total Latent | | :--- | :--- | :--- | :--- | :--- | :--- | | People (Seated, office) | 10 | 210 | 180 | 2,100 | 1,800 | | People (Light work) | 5 | 420 | 600 | 2,100 | 3,000 | | Lighting (Fluorescent) | 2,000 W | 3.4 BTU/W | 0 | 6,800 | 0 | | Equipment (Computers) | 15 | 350 | 0 | 5,250 | 0 | | Equipment (Copier) | 1 | 1,200 | 1,000 | 1,200 | 1,000 | | Infiltration (Air changes) | 0.5 ACH | 1.08 x CFM x ΔT | 0.68 x CFM x ΔW | See formula | See formula | = Grand Total Sensible / (1

^